Pentair UltraTemp Low Refrig Alarm

The LOW REFRIG alarm on a Pentair UltraTemp indicates the refrigerant low pressure switch has opened. This means pressure in the refrigerant system has dropped below safe operating levels.

This alarm can be caused by refrigerant leaks, cold weather, or airflow restrictions across the evaporator coil.

Pentair UltraTemp Low Refrig Alarm

Common Causes

Refrigerant Issues

  • Low refrigerant charge: Leak in the system
  • Refrigerant leak: At joints, valves, or heat exchanger

Environmental Conditions

  • Air temperature too cold: Heat pumps have minimum operating temperatures
  • Water temperature too cold: Below safe operating range

Airflow Problems

  • Fan motor not running
  • Bad fan capacitor
  • Fan blade slipping or broken
  • Debris blocking evaporator coil
  • Shrubs or obstacles restricting airflow

Component Failures

  • Bad low pressure switch
  • TXV (thermal expansion valve) stuck closed
  • Restricted filter drier

Troubleshooting Steps

Step 1: Check Environmental Conditions

  • What is the outdoor air temperature?
  • What is the water temperature?
  • Heat pumps typically need air temps above 50F (10C) for heating
  • If too cold, wait for temperatures to rise

Step 2: Inspect Fan Operation

  1. With heat pump running, verify fan is spinning
  2. Listen for unusual noises
  3. Check that fan blade is not slipping on shaft
  4. Verify fan blade is not cracked or damaged

Step 3: Check Fan Capacitor

  1. Turn off power to heat pump
  2. Locate fan capacitor
  3. Check for bulging, leaking, or damage
  4. Test capacitor with meter if available
  5. Replace if faulty

Step 4: Check Airflow

  1. Remove any debris from around unit
  2. Trim shrubs/vegetation to maintain clearances
  3. Check evaporator coil for dirt or debris
  4. Clean coil if needed (use coil cleaner)

Step 5: Check for Ice

Ice on evaporator coil indicates problems:

  • Low refrigerant charge
  • Restricted airflow
  • Defrost cycle not working

Low Pressure Switch Test

If other troubleshooting fails:

  1. Turn off power to heat pump
  2. Locate low pressure switch
  3. With proper refrigerant charge, switch should be closed
  4. Check resistance - should have continuity when closed
  5. If open with proper charge, replace switch

When HVAC Tech is Needed

Call a licensed HVAC technician if:

  • Refrigerant leak is suspected
  • System needs to be recharged
  • TXV appears to be stuck
  • Filter drier needs replacement
  • Compressor issues are suspected

Required Clearances

Proper clearances ensure adequate airflow:

LocationMinimum Clearance
Sides24 inches
Top (discharge)48 inches
Back12 inches
Front (service access)24 inches

Prevention

  • Maintain proper clearances around unit
  • Keep coils clean
  • Trim vegetation regularly
  • Have refrigerant charge checked annually
  • Don't operate in temperatures below manufacturer limits

Start Your 30-Day Free Trial

Stop losing jobs to voicemail. PoolDial answers every call, books appointments, and saves you $2,000+/month in missed revenue.